Place of Origin: | BEIJING CHINA |
---|---|
Brand Name: | GFUVE |
Certification: | CE, ISO9001, KEMA |
Model Number: | TEST-330 5U3I |
Minimum Order Quantity: | 1SET |
Price: | 20000-28000USD/SET |
Packaging Details: | Standard Export Wooden Box |
Delivery Time: | 2-3weeks |
Payment Terms: | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability: | 200SET/MONTH |
Name: | Secondary Current Injection Test System | Application: | Relay Tester And Protection Device Tester |
---|---|---|---|
Function: | Protection Device And Relay Test | LCD: | 8 Inch TFT Color LCD |
Accuracy: | 0.1% | Frequency: | 0-1050Hz |
U: | 0-300V | I: | 0-90A |
Weight: | 16.6kg | Binary: | 8 Input, 4 Output |
High Light: | secondary injection test equipment,secondary injection test kit |
Portable Three Phase Secondary Current Injection Relay Test System With 8 Binary input/output
The Test-330 Portable Three Phase Secondary Current Injection Relay Test System is the first choice for applications requiring very high accuracy more than 0.1%. This unit is not only an excellent test set for protection devices of all kinds but also a universal calibrator. It can as a ac or dc current source and voltage, 0-10A, 0-130V accuracy 0.1%.
Its unique accuracy and reliability make the Test-330 ideal for protection and measurement equipment manufacturers for research and development, production and electric power company type testing.
This test-330 relay test system can as a standard current source and voltage source, class 0.1. it can test all kinds of instruments and relay device etc.
Test relay device
Test protection device
Test measurement device
Test RTU
Test instrument
Electrical parameters | |
---|---|
Power voltage | AC220V±10% or AC110V±10%, 50/60Hz±10% |
Time measurement | 0.1ms-999999.999s |
AC current output | |
Phase current output (effective value) | 3 x 0-30A |
Maximum power output | 260VA/phase |
Maximum parallel current output (effective value) | 0-90A |
Long-term allowable working value of phase current (effective value) |
>10A |
Allowable working time of maximum current | >11s |
Accuracy class | <±0.1% |
AC voltage output | |
Phase voltage output (effective value) | 5 x 0-130V |
Line voltage output (effective value) | 0-260V |
Maximum power output | 70VA/phase |
Accuracy class | <±0.1% |
DC current output | |
Output range | -10 to 10A or 3 x 0 to ±10A |
Maximum power output | 200VA |
Accuracy class | <±0.1% |
DC voltage output | |
Output range | 0-300V or 5 x 0 to ±130V |
Maximum output power | 130VA |
Accuracy class | <±0.1% |
Binary input | |
Idle contact | 1-20mA, 24V (DC) |
Electric potential contact | 250V/0.5A (DC) |
Binary output | |
Idle contact | 250V/0.5A (DC) |
Rated output | |
Frequency error | <±0.01Hz |
Phase error | <±0.1% |
Waveform distortion | <±0.3% (fundamental wave) |
Time error | <40µs |
Output frequency | 0-1050Hz |
Superposed harmonic wave | 0-21times |
Mechanical parameters | |
Dimensions (L×W×H) (mm) | 360x195x375 |
Weight (kg) | 16.6 |
Environmental conditions | |
Use range | 0°C to 45°C |
Storage range | -25°C to 70°C |