| Place of Origin: | CHINA |
|---|---|
| Brand Name: | GFUVE |
| Certification: | CE IEC ISO |
| Model Number: | GF106T |
| Minimum Order Quantity: | 1 Set |
| Price: | Negotiable |
| Packaging Details: | Alu-Box |
| Delivery Time: | 3-4Weeks |
| Payment Terms: | Western Union, MoneyGram, T/T, , L/C |
| Supply Ability: | 200Sets/Month |
| NAME: | CT PT ANALYZER | Accuracy: | 0.2%, 0.5% |
|---|---|---|---|
| Power Supply: | AC 220V±10% Or AC 110V±10%, 50/60Hz | Excitation Voltage Output: | 0-2500Vrms |
| Excitation Current Output: | 0-5Arms (20A Peak-value) | Overall Dimension (L X W X H) (mm): | 400 X 250 X 250 |
| High Light: | transformer test instruments,circuit breaker analyzer |
||
| I. Current Transformer (CT) | II. Voltage Transformer (PT) |
|---|---|
| 1. Magnetization curve | 1. Excitation characteristic test |
| 2. Transformation ratio test | 2. Transformation ratio test |
| 3. Polarity | 3. Polarity |
| 4. 5% and 10% error curve | 4. Withstand test of power frequency alternating current |
| 5. Current Injecting | 5. Degauss |
| 6. Degauss | 6. Calculation of knee point value |
| 7. Withstand test of power frequency alternating current | 7. Actual secondary load test |
| 8. Automatic calculation of excitation knee point value |
8. Resistance test |
| 9. Actual secondary load test | |
| 10. Resistance test | |
| Electrical parameters | ||
|---|---|---|
| Accuracy | 0.2%, 0.5% | |
| Power supply | AC 220V±10% or AC 110V±10%, 50/60Hz | |
| Excitation voltage output | 0-2500Vrms, | |
| Excitation current output | 0-5Arms (20A peak-value) | |
| Large current output | 0-1000A | |
| Electrical parameters - continued | ||
| Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
| Secondary winding DC resistance measurement | Range | 0.1-300Ω |
| Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
| Secondary actual load measurement | Range | 5VA-1000VA |
| Accuracy | ≤0.5% (0.2%RD+0.3%RG)±0.1VA | |
| CT/PT phase error measurement | Accuracy | ±4min |
| Resolution | 0.01min | |
| CT ratio error measurement | Range | ≤25000A/5A(5000A/1A) |
| Accuracy | ≤0.5% | |
| PT ratio error measurement | Range | 1-500KV |
| Accuracy | ≤0.5% | |
| Standards | ||
| Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-2-2012 |
|
| Safety standards | GB 4793.1-2007 | |
| EMC | EMC standard 89/336/EEC | |
| FCC Subpart B of Part 15 Class A | ||
| IEC 1000-4-2 /3 /4 /6 | ||
| Mechanical parameters | ||
| Overall dimension (L x W x H) (mm) | 400 x 250 x 250 | |
| Weight (kg) | ≤22 | |
| Environmental conditions | ||
| Relative humidity | 90RH% | |
| Operating temperature | -10°C to +40°C | |
| Altitude | ≤1000m | |
![]()
![]()